Basement bedroom check
Enter what you measured and see each number against the model code's minimums, item by item.
The sample numbers are made up. Replace them with your measurements.
This compares your numbers with the model International Residential Code only. States and cities adopt the model code and amend it, and some change the ceiling height or escape opening rules, so your local numbers can differ. Whether a room can be used as a bedroom is decided by your local building department. This tool is not a permit decision.
What the tool checks
Each line compares one number with the model code's minimum. Section numbers are shown for the 2021 edition and the 2024 edition, which renumbered chapter 3.
- Ceiling height: 7 ft 0 in for a habitable space (2021 IRC R305.1; 2024 IRC R313.1).
- Beams, girders and ducts: in a basement with habitable space they may come down to 6 ft 4 in above the finished floor (2021 IRC R305.1, exception 3).
- Net clear opening area: 5.7 square feet, or 5 square feet for a grade-floor opening (2021 IRC R310.2.1; 2024 IRC R319.2.1). The tool computes width times height divided by 144 and shows it rounded down, so a figure never looks like it meets the limit when it does not.
- Net clear height and width: 24 inches and 20 inches. Both are needed at the same time as the area: a 20 by 24 inch opening meets both sizes and still falls short on area (2021 IRC R310.2.2; 2024 IRC R319.2.2).
- Sill height: the bottom of the clear opening no more than 44 inches above the finished floor (2021 IRC R310.2.3; 2024 IRC R319.2.3).
The last line, "How it opens, wells and doors", is always NEEDS CHECK. The dimensions have to come from opening the window the normal way from inside, and it has to open without keys, tools or special knowledge (2021 IRC R310.1.1). A window well below ground has its own minimum size and needs a ladder or steps when it is deeper than 44 inches (2021 IRC R310.4). A door used as the opening has its own rules (2021 IRC R310.3). The tool keeps wells and doors to this note and does not measure them.
Model code, adopted code, your department
The International Code Council publishes the model code. A state or city adopts a version of it, often an older one, and amends it. Among the sources read for this page, Washington's residential code amends parts of R310 and Oregon's 2023 residential code amends R310.1. What applies to your house is the code your local building department enforces.
That department also decides whether a room can be used as a bedroom. This tool does not say a room is or is not one. It does not check smoke and carbon monoxide alarms, light and ventilation, minimum room size, heating, electrical or structure. It is not a permit decision.
Worked example with made-up numbers
A finished ceiling 7 feet 2 inches high, a duct at 6 feet 6 inches, and a window with a net clear opening 28 inches wide and 32 inches high whose sill is 40 inches above the floor.
| Item | Result | Detail |
|---|---|---|
| Ceiling height | PASS | 7 ft 2 in entered; the model minimum for a habitable space is 7 ft 0 in. |
| Lowest beam, girder or duct | PASS | 6 ft 6 in entered, measured from the finished floor; the model lets beams, girders and ducts in a basement with habitable space come down to 6 ft 4 in. |
| Net clear opening area | PASS | 6.22 sq ft (28 in by 32 in, rounded down); the model minimum is 5.7 sq ft. |
| Net clear opening height | PASS | 32 in entered; the model minimum net clear height is 24 in. |
| Net clear opening width | PASS | 28 in entered; the model minimum net clear width is 20 in. |
| Sill height (bottom of the clear opening) | PASS | 40 in entered; the model allows 44 in at most from the finished floor to the bottom of the clear opening. |
| How it opens, wells and doors | NEEDS CHECK | The net clear size has to come from opening the window the normal way from inside, and it has to open without keys, tools or special knowledge. Measure it that way. |
Sources
Read on November 20, 2026. The primary text is the ICC's own free digital code, chapter 3 of the 2021 and the 2024 International Residential Code (ICC marks both as historical versions). The other documents below are building departments and the ICC that quote the code. Read the code text yourself, or ask your building department, before you rely on any figure.
- ICC, 2021 International Residential Code, chapter 3: R305.1 and R305.1.1 (ceiling height; exception 3 lets beams, girders and ducts in a basement with habitable space project to 6 feet 4 inches), R310.1, R310.2.1 to R310.2.3 (5.7 square feet, 5 for grade-floor openings, 24 inches high, 20 inches wide, sill at most 44 inches), R310.4 (area wells) and R310.7 (alterations of existing basements): codes.iccsafe.org. 2024 edition: the same rules appear as R313.1 and R313.1.1 and as R319.1, R319.2.1 to R319.2.3 and R319.4: codes.iccsafe.org.
- Boulder County, Publication B10, "Emergency Escape and Rescue Openings", written for the 2021 IRC, Section R310: 5.7 square feet (5 for grade-floor openings) in R310.2.1, 24 inch height and 20 inch width in R310.2.2, 44 inch maximum sill height in R310.2.3, windows under decks in R310.2.4, window ("area") wells in R310.4 with 9 square feet and 36 inches, ladders or steps over 44 inches deep in R310.4.2, and operation without keys, tools or special knowledge in R310.1.1: bouldercounty.gov. No publication date on the page.
- City of Boise, IRC Code Handout #434, dated 01/2022 (edition not named), R305.1 and R305.1.1: 7 feet for habitable space and for basement portions containing it; beams, girders, ducts or other obstructions in a basement containing habitable space may project to within 6 feet 4 inches of the finished floor; 6 feet 8 inches, and 6 feet 4 inches at obstructions, for basement portions without habitable space: cityofboise.org.
- Jefferson County, Colorado, "Ceiling Heights" (2024 IRC): R313.1 gives 7 feet, with a 6 feet 4 inch exception at obstructions: jeffco.us. And "Emergency Escape and Rescue Openings" (2024 IRC): R319.1, R319.2.1 with 5.7 and 5 square feet, 24 and 20 inches, and R319.4.2 for ladders: jeffco.us.
- ICC, "Session 1 and 31, 2024 IRC Significant Changes": the chapter 3 reorganization, with ceiling height and escape openings among the renumbered sections (R305 to R313 and R310 to R319): iccsafe.org.
- ICC, 2018 code change proposal "IRC 3-2 EERO" (September 27, 2018), which shows the existing R310.2.1 to R310.2.3 wording: net clear opening of not less than 5.7 square feet, 24 inches high, 20 inches wide, and the bottom of the clear opening not greater than 44 inches above the floor: iccsafe.org.
- Washington State, WAC 51-51-03100 (R310 as adopted, versions until and from March 15, 2024): lawfilesext.leg.wa.gov. Oregon, 2023 Oregon Residential Specialty Code, R310 amendment: oregon.gov.
Limits
- Sloped ceilings, habitable attics and other special cases follow other rules. The tool checks a flat finished ceiling.
- Section numbers: checked against the ICC text of the 2021 and 2024 IRC. States and cities adopt other editions and amend them, so your building department's version is the one that counts.
- Existing basements: under R310.7 (2021) a basement that is only altered or repaired needs an escape opening only for a new sleeping room, and an existing window that is the only opening may be accepted at 4 square feet and 22 inches in height where the code allows it. This tool checks the full new-opening numbers; ask the building department which applies.
- Limits on the inputs: ceiling 4 to 12 feet (whole feet, inches 0 to 11.9), opening sizes 1 to 120 inches, sill 0 to 120 inches.